| 1 |
Terminal-block product classification |
IEC 60947-7-1; GB/T 14048.7 |
The product should be designed as a terminal block for copper conductors, with clearly declared electrical ratings, connection method, conductor range, and installation conditions. |
Technical datasheet, product drawings, rating label, and test report issued for the exact model. |
Critical |
| 2 |
DIN rail compatibility |
IEC 60715 |
The housing and locking foot should correctly fit the specified standardized rail profile, commonly TS35 × 7.5 mm or TS35 × 15 mm for industrial control cabinets. |
Rail-profile drawing, dimensional inspection record, and installation compatibility statement. |
Critical |
| 3 |
Rated voltage and insulation performance |
IEC 60947-7-1 |
Rated operational voltage, rated insulation voltage, clearance, and creepage distance must be consistent with the declared application category and pollution environment. |
Electrical rating table, insulation test results, creepage and clearance drawings. |
Critical |
| 4 |
Current-carrying capacity and temperature rise |
IEC 60947-7-1 |
The declared current rating should be supported by temperature-rise testing using the specified conductor size, tightening torque, number of poles, and installation arrangement. |
Temperature-rise test report, derating curve, conductor specification, and torque requirements. |
Critical |
| 5 |
Connection reliability and pull-out resistance |
IEC 60999-1; IEC 60947-7-1 |
Screw and screwless clamping units should securely accommodate the declared conductor types and sizes without unacceptable loosening, damage, or conductor movement. |
Mechanical strength test, conductor pull-out test, torque specification, and vibration test data where applicable. |
Critical |
| 6 |
Protective conductor and grounding version |
IEC 60947-7-2 |
Protective conductor terminal blocks should provide a reliable electrical connection to the mounting rail or designated protective conductor path, with appropriate green-yellow identification. |
Protective-circuit continuity test, corrosion test data, rail-contact design, and marking details. |
High |
| 7 |
Flammability and insulating-material performance |
IEC 60695-11-10; IEC 60947-7-1 |
Insulating parts should use suitable electrical-grade materials with documented resistance to heat, flame, and abnormal temperature conditions required by the application. |
Material declaration, flammability classification, glow-wire or flame-test report, and thermal-aging information. |
High |
| 8 |
Use in control panels and machinery |
IEC 60204-1; IEC 61439-1 |
The terminal block should support the wiring, identification, segregation, accessibility, and verification requirements of machinery electrical equipment or low-voltage assemblies. |
Application guide, assembly instructions, wiring examples, and compatibility information for enclosure systems. |
High |
| 9 |
North American market suitability |
UL 1059 |
For projects requiring North American acceptance, the terminal block configuration, spacing, wire range, temperature rating, and marked electrical ratings should meet the applicable terminal-block requirements. |
Certification or listing information for the exact construction, model family, and intended field wiring conditions. |
Project-Based |
| 10 |
Environmental compliance and traceability |
RoHS Directive 2011/65/EU and Amendment (EU) 2015/863 |
Materials should comply with applicable restricted-substance limits, while production lots should remain traceable through documented inspection and change-control procedures. |
RoHS declaration, material composition records, batch traceability, inspection plan, and change-notification procedure. |
High |