• page_head_bg

Products

Jut2-10 10mm2 universal Din Rail Terminal Block screwfix feed through terminal block

Short Description:

BrieflySteel locking wire structure terminal, copper conductor, flame retardant nylon insulation Frame, widely used in industrial equipment, transportation, construction, security, communications and other fields.

Working current: 57 A, Operating Voltage: 800V.

Wiring method: screw connection.

Rated wiring capacity: 10 mm2

Installation method: NS 35/7.5, NS 35/15


Technical Data

business data

download

Certification

Product Tags

Advantage

JUT2 combination-type wiring terminal series have following advantages:
●Terminals with general-purpose mounting feet, which enables quick installation on U shaped track NS 35 and G shaped track NS 32;
●Closed bolt leading hole will not only facilitate operation of screwdrivers, also prevent the bolt from dropping out;
●Potential distribution via fixed bridges in the terminal center or insertion bridges in the clamping space;
●Two ends on the top with white marking system to realize uniformed sign;
●The JUT universal screw terminal block series has the typical features which are decisive for practical applications;
●The insulating shell raw material is Nylon 66(PA66), with high mechanical intensity, good electric property, and super flexibility.
●General auxiliaries, such as the end plate, segment spacer, and spacer, are attached for terminal with multiple sections.

Details parameters

Product Image    
Product number JUT2-10 JUT2-10PE
product type Din rail terminal block PE terminal block
Mechanical structure screw type screw type
layers 1 1
Electric potential 1 1
connection volume 2 2
Rated cross section 10 mm2 10 mm2
Rated current 57A  
Rated voltage 800V  
open side panel yes no
grounding feet no yes
other The connecting rail needs to install the rail foot F-NS35
Application field Widely used in electrical connection, industrial
color beige, customizable Yellow/green
Stripping length 12mm 15mm
Rigid Conductor Cross Section 1.5mm²  16mm² 1.5mm²  16mm²
Flexible conductor cross section 1.5mm²  10mm² 1.5mm²  16mm²
Rigid Conductor Cross Section AWG 20-6 20-6
Flexible Conductor Cross Section AWG 20-6 20-6
thickness 10mm 10mm
width 42mm 40.3mm
high    
NS35/7.5 high 47.5 mm 47.7mm
NS35/15 high 55mm 55.2mm
NS15/5.5 high    
Flame retardant grade, in line with UL94 V0 V0
Insulation Materials PA PA
Insulation material group I I
  standard test IEC 60947-7-1 IEC 60947-7-1
Rated voltageIII/3 800V  
Rated currentIII/3 57A  
Rated surge voltage 9.8kv 9.8kv
Overvoltage class III III
pollution level 3 3
Surge Voltage Test Results Passed the test Passed the test
Power frequency withstand voltage test results Passed the test Passed the test
Temperature rise test results Passed the test Passed the test
Ambient temperature (operating) -60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.) -60 °C — 105 °C (Maximum short-term operating temperature, electrical characteristics are relative to temperature.)
Ambient temperature (storage/transport) -25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C) -25 °C — 60 °C (short term (up to 24 hours), -60 °C to +70 °C)
Ambient temperature (assembled) -5 °C  70 °C -5 °C  70 °C
Ambient temperature (execution) -5 °C  70 °C -5 °C  70 °C
Relative Humidity (Storage/Transportation) 30 %  70 % 30 %  70 %
RoHS No excessive harmful substances No excessive harmful substances
Connections are standard IEC 60947-7-1 IEC 60947-7-1

  • Previous:
  • Next:

  •